Vue de la page 86
Application Parameters
S1A53838 09/2011 87
Skip Frequencies
Do not set the skip frequency bands so that they overlap.
While the drive will not operate within these skip frequency bands during steady state operation, skip frequency
bands are ignored by the drive during motor acceleration and deceleration.
Code Name / Description Adjustment range Factory setting
F270 [Jump frequency 1]
Skip frequency 1 midpoint
0.0 to [Max frequency] (FH) Hz 0.0 Hz
F271 [Jump bandwidth 1]
Skip frequency 1 bandwidth 0.0 to 30.0 Hz 0.0 Hz
F272 [Jump frequency 2]
Skip frequency 2 midpoint 0.0 to [Max frequency] (FH) Hz 0.0 Hz
F273 [Jump bandwidth 2]
Skip frequency 2 bandwidth 0.0 to 30.0 Hz 0.0 Hz
F274 [Jump frequency 3]
Skip frequency 3 midpoint 0.0 to [Max frequency] (FH) Hz 0.0 Hz
F275 [Jump bandwidth 3]
Skip frequency 3 bandwidth 0.0 to 30.0 Hz 0.0 Hz