DS7400Xi Ver. 3+ Reference Guide Copyright © 2004 Detection Systems, Inc. P/N: 28995K Page 19
Multiple Keypad Use: One keypad only must be used on the
option bus, at any address from 11 - 14, and must meet the
following requirements:
- The keypad must be mounted to the front of the control
enclosure OR mounted within the same room as the control
equipment. The wire is run in conduit (or equivalently protected
against mechanical injury) within 20 ft. (6.1m) of the control
equipment.
- All other keypads should be connected to the keypad bus and
may be placed as needed (within the noted wiring limitations in
the installation manual).
- One keypad must be assigned as address 1.
6.12 Open/Close Report Control Programming
Open and Close Reports: If programmed, these reports are
sent when the system is armed or disarmed. They may be sent
independently for the opening and closing of each partition, or
the first partition to open and the last partition to close may send
the reports.
Alternate between both Phone Numbers: If programmed, open
and close reports will be sent to phone number one first. If phone
number one does not pick-up, the control panel will alternate to
phone number two. If phone number two does not pick-up, the
control panel will alternate back to phone number one. It will
alternate between both phone numbers until successful.
6.13 Report Programming
Reports: For pulse formats, reports are programmed by entering
data in the reporting and extended digits. The report will send the
data programmed for each event. For SIA and Contact ID, the
report formats are fixed and may be activated by placing a 1 in
the reporting digit.
- To disable a report, enter a 0 in the reporting digit.
- To send the Man No. along with Open and Close reports,
program an "F" (enter [*] [5] at the keypad) in the extended
digit.
Keypad Fire Alarm: This report is sent when a fire alarm has
been activated by the “A” emergency key.
Keypad Fire Restoral: This report is sent when a keypad fire
alarm has been restored using the [System Reset] command.
Keypad Emergency Alarm: This report is sent when an
emergency alarm has been activated using the “B” emergency
key.
Keypad Panic: This report is sent when an emergency alarm
has been activated using the “C” emergency key.
Keypad Tamper: For keypads fitted with a wall tamper switch,
this report is sent when the keypad is removed from the wall.
Keypad Tamper Restoral: For keypads fitted with a wall tamper
switch, this report is sent when the keypad is properly replaced
on the wall after experiencing a tamper condition.
Zone Function Alarm: An alarm report is sent when a zone
alarm occurs. Alarm reports are enabled by zone function. Program
this report for any zone functions you wish to send an alarm report
about. For local zones (no reports), do not program an alarm
report. The zone number will automatically be sent for this report
in SIA or Contact ID format.
Zone Function Restoral: This report is sent when the zone alarm
is cleared. The zone number will automatically be sent for this
report in SIA or Contact ID format.
Zone Function Trouble: This report is sent when a zone trouble
condition occurs. This can be an open circuit, if the zone is
programmed for “trouble on open”, a multiplex tamper switch being
activated, or a multiplex zone not communicating with the control
panel. The zone number will automatically be sent for this report
in SIA or Contact ID format.
Zone Function Trouble Restoral: This report is sent when the
trouble condition is cleared. The zone number will automatically
be sent for this report in SIA or Contact ID format.
Zone Function Bypass: This report is sent when a zone is
bypassed. (Note: Fire zones can never be bypassed.) Zone bypass
reports for non-24 hour zones are sent with the closing report.
Bypass reports for 24 hour zones are sent when the zone is
bypassed. If a zone is force armed, the bypass report is sent with
the partial close report. If a 24 hour or non-24 hour zone is custom
armed, the bypass report is sent with the partial close report.
Zone Function Bypass Restoral: This report is sent when the
zone bypass is cleared. For non-24 hour zones the bypass restoral
is sent with the open report. Bypass restoral reports for 24 hour
zones are sent when the zone is manually restored. The bypass
restoral report for a zone that was force armed is sent when the
zone is restored. If a 24 hour or non-24 hour zone was custom
armed, the bypass restoral is sent with the open report.
Open: This report is sent when the system has been disarmed.
In SIA or Contact ID formats, the user number for the person who
disarmed the system will be sent with this report. To send the
user number along with an Open report in other formats, program
the extended digit of the report as *5. In Contact ID format, the
partition number will also be sent along with this report. The Open
report will only be sent if a Close report was sent previously.
Close: This report is sent when the system has been armed. In
SIA or Contact ID formats, the user number for the person who
armed the system will be sent with this report. To send the user
number along with a Close report in other formats, program the
extended digit of the report as *5. In Contact ID format, the partition
number will also be sent along with this report.
Duress: This report is sent when the system is disarmed using a
duress code. The user number is not sent with this report.
Partial Close: This report is sent when the system is armed
partially, or force armed.
First Open After Alarm: This report is sent when the system is
disarmed after an alarm has occurred.
Low Battery: This report is sent when a low battery condition
occurs.
Battery Restoral: This report is sent when a low battery condition
restores.
AC Fail: This report is sent when an AC failure condition occurs.
This report may be delayed in address 0197.
AC Failure Report Delay
The AC power loss report can be programmed to delay for up to
254 minutes (see address 0197). (The same delay would also
apply to the AC restoral report.)
- If another report is sent during this delay period, the AC fail
report will be sent along with this report.
- If the AC power restores during this delay period, the AC loss
report will not be sent.
- Programming address 0197 as FF causes the report to be sent
at a random interval of at least 15 minutes, but no more than 2
hours after the AC failure occurs.
AC Restoral: This report is sent when an AC failure condition
restores.
Communicator Test/System Normal: This report is sent at the