Code Alarm PC 7500 Spécifications

Naviguer en ligne ou télécharger Spécifications pour Les démarreurs à distance Code Alarm PC 7500. Code Alarm PC 7500 Specifications Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 50
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
12 Clintonville Road, Northford, CT 06472-1610 USA • TEL: (203) 484-7161 • FAX: (203) 484-7118
www.gamewell-fci.com
Copyright © 1998
Honeywell International Inc.
All Rights Reserved
Published in U.S.A.
7100 Series Fire Alarm Control
Installation/Operating Manual
Document: 9000-0447
Print Date: 6/6/07 Rev. I
P/N 9000-0447 Rev. I ECN: 06-528
Vue de la page 0
1 2 3 4 5 6 ... 49 50

Résumé du contenu

Page 1 - Installation/Operating Manual

12 Clintonville Road, Northford, CT 06472-1610 USA • TEL: (203) 484-7161 • FAX: (203) 484-7118 www.g

Page 2

9000-0447 Rev. I Page 4 of 42 1.0 System Overview 1.1 Description The Gamewell-FCI 7100 is a multiprocessor-based analog/addressable system, de-signe

Page 3

9000-0447 Rev. I Page 5 of 42 1.2.2 Optional Features • Class A Module (CAOM) with Disconnect Switches for NACs and SLCs • Digital Alarm Communica

Page 4

9000-0447 Rev. I Page 6 of 42 1.4.3 Municipal Circuit Option Module (MCOM) The MCOM Module can trip a Local Energy City Master Box, or operate in re

Page 5 - Installation Precautions

9000-0447 Rev. I Page 7 of 42 Notification Appliance Circuits (TB1) • Two (2) regulated power outputs • Power-limited • Supervised • Non-coded • Ma

Page 6 - Documentation Feedback

9000-0447 Rev. I Page 8 of 42 Battery Connection (TB7) • Supervised • 24 VDC nominal • Maximum battery size 31 AH • Non-power-limited • 0.6 A max.

Page 7

9000-0447 Rev. I Page 9 of 42 2.0 Installation 2.1 General Components are ordered and shipped in separate packaging for the enclosure and Basic Syste

Page 8

9000-0447 Rev. I Page 10 of 42 Figure 5 7100 Wire Connections

Page 9

9000-0447 Rev. I Page 11 of 42 3.0 Basic System Module (BSM) Table 3-1 Field Wiring Connections Designation Description Comments TB1-1 NAC Circ

Page 10 - 1.0 System Overview

9000-0447 Rev. I Page 12 of 42 Table 3-2 LEDs Jumpers Designation Description Comments LEDs LED25 Yellow Line 1 Trouble LED26 Yellow Line 2 Tro

Page 11 - 1.4 Optional Modules

9000-0447 Rev. I Page 13 of 42 3.2 Relay Connections System Trouble Contacts • TB2-1 Normally Open • TB2-2 Common • TB2-3 Normally Closed Transfe

Page 12 - 1.5 Specifications

9000-0447 Rev. I i Fire Alarm System Limitations While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance! This

Page 13

9000-0447 Rev. I Page 14 of 42 Table 3-3 Battery Standby Chart Qty Module Description Supv. Current Alarm Current Total Supv. Current Total A

Page 14

9000-0447 Rev. I Page 15 of 42 3.3 Notification Appliance Circuits The 7100 provides two (2), 24 VDC Class B, Style Y notification appliance circuit

Page 15 - 2.1 General

9000-0447 Rev. I Page 16 of 42 3.4.1 Style 7 Signaling Line Circuit Installation When using a Control Module as a Notification Appliance Circuit (NA

Page 16 - Page 10 of 42

9000-0447 Rev. I Page 17 of 47 3.5 Analog Sensors The 7100 accommodates only Gamewell-FCI approved, UL Listed, analog sensors and bases. See the Gam

Page 17

9000-0447 Rev. I Page 18 of 42 3.9 Optional Modules 3.9.1 Class A Option Module (CAOM) The Class A Option Module (CAOM) provides Class A signaling f

Page 18 - 3.1 Power

9000-0447 Rev. I Page 19 of 42 3.10 Digital Communicator Operation (7100-D Model) The 7100-D digital communicator model features numerous formats f

Page 19 - 3.2 Relay Connections

9000-0447 Rev. I Page 20 of 42 3.12 7100-D DACT Event Reporting Codes The 7100-D DACT event reporting codes are shown in Table 3-6 below: Table 3-6

Page 20

9000-0447 Rev. I Page 21 of 42 3.13 Telephone Requirements • DC Ringer Equivalence Number (REN) = 0.5B • AC Ringer Equivalence Number = 1.3 • Com

Page 21

9000-0447 Rev. I Page 22 of 42 3.18 Optional Accessories 3.18.1 LCD-7100 Serial Remote Annunciator The LCD-7100 Serial Remote Annunciator provides a

Page 22

9000-0447 Rev. I Page 23 of 42 4.0 Programming/Operation Instructions 4.1 LED Indicators Table 4-1 LED Indicators Designation De

Page 23

9000-0447 Rev. I ii reduced terminal contact pressure and difficulty with screw terminal removal. Disconnect all sources of power before servicing,

Page 24 - 3.9 Optional Modules

9000-0447 Rev. I Page 24 of 42 4.2 Panel Switches Table 4-2 Switches Designation Comments Alarm Acknowledge Silences the panel

Page 25

9000-0447 Rev. I Page 25 of 42 Sensors occupy Addresses 01-99 on the signaling line circuits. Sensors are ion, photoelectronic, or thermal. They are

Page 26

9000-0447 Rev. I Page 26 of 42 [GAIN ] Type password for level 3: [ACCESS] 000000 keypad: enters password (shows as “XXX…” on display) Main Any se

Page 27 - 3.17 Repairs

9000-0447 Rev. I Page 27 of 42 5.2 CONFIG. Menu Selections AUTO Is the selection used to either initialize the system or update it. GLOBAL Is the

Page 28

9000-0447 Rev. I Page 28 of 42 Table 5-1 7100 Series Menu System Menu Tree Display and Selections [MAIN] 1: Config 2: Walk/Drill 3:I/O 4: Clock

Page 29 - 4.1 LED Indicators

9000-0447 Rev. I Page 29 of 42 [SET ] 1: Verification 2: Sensitivity [DEFAULTS] 3: PAS 4: Multilevel 1: Opens Set Default Verify Options Menu. 2

Page 30 - 4.2 Panel Switches

9000-0447 Rev. I Page 30 of 42 [CODED] 1: Set Day Alarm (MT60) Config [PATTS] to select condition Main Config Global Codes <>: selects

Page 31

9000-0447 Rev. I Page 31 of 42 [SELECT] Loop, Address: 1,001 [DEVICE] Key in or use <,> # keys: enters SLC & address (restriction: Address

Page 32

9000-0447 Rev. I Page 32 of 42 [CONFIG] 1: Type 2: General Resp 3: Groups [L,AAA ] 5: Location 6: View 7: Copy L,AAA 1: Opens Set Output Type Menu

Page 33 - 5.2 CONFIG. Menu Selections

9000-0447 Rev. I Page 33 of 42 [CONFG] 0:Options 1:Line1 2:Line2 [DACT ] 3:Account1 4:Account 2 0: Opens DACT Options Menu. 1: Opens Phone L

Page 34

9000-0447 Rev. I iii • Smoke particles may be blown away from detectors by air outlets. • Smoke particles may be drawn into air returns before re

Page 35

9000-0447 Rev. I Page 34 of 42 5.3 WALK / DRILL Menu Selections Drill ON/OFF Is a simple ON or OFF selection. ON will activate the NACs, while OFF

Page 36

9000-0447 Rev. I Page 35 of 42 [Walk/] 1: Drill (OFF) 2:Audble Test (OFF) [DRILL] 3: Silent Test (OFF) 1: Toggles Fire Drill ON/OFF. 2: Toggles Aud

Page 37

9000-0447 Rev. I Page 36 of 42 5.5 CLOCK Menu Selections Time Is set in 24 hour notation. It is set with hours then minutes “HHMM”. Date Is set as

Page 38

9000-0447 Rev. I Page 37 of 42 [SET ]1: Time 2: Date 3: Night [CLOCK]4: Weekend 5: Holidays 1: Opens Set Time Menu. 2: Opens Set Date Menu. 3: Op

Page 39

9000-0447 Rev. I Page 38 of 42 5.6 LOG Menu Selections Display Log Opens the System Display to all events in the buffer memory. Print Log Sends the

Page 40 - 5.4 I/O Menu Selections

9000-0447 Rev. I Page 39 of 42 [VIEW] 1:Display Log 2: Print Log [LOG ] 3:Clear Log 4:Sens. Report 1: Opens Show Events Menu. 2: Opens Print Lo

Page 41

9000-0447 Rev. I Page 40 of 42 6.0 Power Up Procedure 6.1 General Ensure that all cables and optional modules (if any) are installed and secured per

Page 42 - 5.5 CLOCK Menu Selections

9000-0447 Rev. I Page 41 of 42 Table 6-1 7100 Series Device Types and Functions # Device Type Physical Response Action in Alarm Condition 1 Ion S

Page 43

9000-0447 Rev. I Page 42 of 42 Figure 11 Power-Limited/Non Power-Limited Wiring

Page 44 - 5.7 INFO Menu Selection

9000-0447 Rev. I Limited Warranty Honeywell International Inc. warrants products manufactured by it to be free from defects in materials and workma

Page 45

9000-0447 Rev. I iv Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING -

Page 46 - 6.3 Automatic Configuration

9000-0447 Rev. I Gamewell-FCI12 Clintonville RoadNorthford, CT 06472-1610 USA203-484-7161fax: 203-484-7118www.ga

Page 47 - Non-Reporting Ion Non latch

9000-0447 Rev. I v Documentation Feedback Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggest

Page 48

9000-0447 Rev. I Page 1 of 42 TABLE OF CONTENTS 1.0 System Overview...

Page 49 - Limited Warranty

9000-0447 Rev. I Page 2 of 42 3.16 FCC Required Information ......

Page 50

9000-0447 Rev. I Page 3 of 42 Figure 1 Basic System Module (BSM)

Commentaires sur ces manuels

Pas de commentaire