Power Quality Metering
Compliance Monitoring*
w EN 50160 compliance monitoring
w IEC 61000-4-7 harmonics & inter-harmonics
w IEC 61000-4-15 flicker
w CBEMA/ITIC
w IEEE 519 and IEEE 1159
Waveform Recording
The meters can simultaneously capture all
voltage and current channels.
w Sub-cycle disturbance capture
w Record back-to-back waveforms for up to
several seconds
w Display and compare multiple waveforms in
PEGASYS software
w Record 7 cycles at 256 samples/cycle to 96
cycles at 16 samples/cycle with the 7600 ION
w Record 14 cycles at 128 samples/cycle to 96
cycles at 16 samples/cycle with the 7500 ION
Outage Detection
Setpoints let you detect, record, and report
outages in real-time, including duration, date,
time, and relation to other system conditions.
Out-of-Limit Detection
The meters offer accurate and reliable setpoint
capabilities for the detection, recording, and real-
time reporting of frequency variations, voltage or
current phase imbalances, loss of voltage or
current phase, power factor variations, etc.
Performance Indicators
The units can be configured to meter a wide
range of utility performance indicators, including:
w Total outage time (in seconds)
w Out-of-tolerance duration for total harmonic
distortion, voltage, frequency, power factor
and hundreds of other definable indices
Harmonic Distortion Metering
Complete harmonic distortion metering,
recording and real-time reporting, up to the 63rd
harmonic, (127th for 7600 ION via PEGASYS
software), for all voltage and current inputs.
w Individual harmonics, (including magnitude,
phase and inter-harmonics for the 7600 ION)
w Total even harmonics
w Total odd harmonics
w Total harmonics (even + odd)
w K-factor, Crest factor
Symmetrical Components*
Zero, negative and positive sequences including
phase & magnitude for voltage & current inputs.
Identify harmful voltage & current unbalances in
equipment before they cause damage.
Disturbance Detection
High-speed setpoints allow the reliable detection
and recording of events, sequence-of-events,
and alarm conditions, including magnitude,
duration and equipment status. Waveform
recorders are configurable and can record all
voltage and current inputs simultaneously.
Control the number of pre-event and post-event
cycles recorded. Trigger waveform recording with
events, external inputs, or manual control.
Sag/Swell Detection
The 7500 ION and 7600 ION incorporate a
dedicated sag/swell capture capability that can
be used to analyze the severity and potential
impact of sags and swells.
w Magnitude and duration data suitable for
plotting on voltage tolerance curves
w Per-phase triggers for waveform recording or
control operations
Transient Capture*
w The 7600 ION can detect and record sub-
cycle transients as short as
60 ms @ 65 Hz,
(78 ms @ 50 Hz)
w Analyze transients by plotting them on a
voltage tolerance (e.g. CBEMA) curve using
our PC-based PEGASYS software
Data & Event Recording
The 7600 ION offers 4 MB (up to 8 MB optional)
of nonvolatile memory for waveform, event and
log storage while the 7500 ION is equipped with
1 MB. Memory can be allocated as needed
ensuring important data is never lost.
Load Profiling
The 7600 ION incorporates 640 channels via 40
data recorders, the 7500 ION provides 320
channels via 20 data recorders. Channel
assignments are configurable for historical trend
recording of energy, demand, voltage, current,
power quality, or any other measured parameter.
Trigger recorders based on time interval, calendar
schedule, alarm/event condition, or manually.
High-Speed Data Recording
High-speed “burst” recording (as fast as 1/2-
cycle intervals) stores detailed characteristics of
disturbances or outages. Trigger recording by a
user-defined setpoint, or from external
equipment. Gated recording logs data only during
the critical event so that memory is conserved.
Coincident Min/Max Recording
Log the values of key parameters or equipment
conditions coincident with an extreme condition,
complete with date/time stamping. For example,
record all feeder voltages and currents at the
moment a peak demand condition occurs.
Multiple display formats are available, including bar
graphs with min/max indicators
Displays a complete range of power parameters
Unique vector diagram with magnitude and phase
angle can help reduce installation time
View THD and individual harmonics through the front
panel display screen
** AAvvaaiillaabbllee oonnllyy oonn 77660000 IIOONN
7600 ION/7500 ION